Light duty vehicle performance testing environment warehouse
Technical solution
(2024 version)
EST Environmental Test Chamber Case
|
USER |
Basic information |
Contract Time |
1 |
Shanghai Delphi |
Light vehicle cold start compartment (-40 ℃) |
2005 |
2 |
Beijing Auto's Foton |
arge motor/battery testing chamber (-40 ℃) |
2012 |
3 |
Beijing Auto's Foton |
Heavy duty motor/battery testing chamber (-40 ℃) |
2012 |
4 |
Shanghai Yada Rubber |
Automotive parts emission compartment (10 ℃ to 55 ℃) |
2017 |
5 |
Chongqing Plastic Union |
Automotive parts emission compartment (10 ℃ to 55 ℃) |
2018 |
6 |
Beijing Auto's Foton |
Light vehicle performance testing environment chamber (-40 ℃) |
2018 |
7 |
Baoding Great Wall |
IMTECH light vehicle emission compartment renovation (-20 ℃) |
2020 |
8 |
Baoding Great Wall |
Vehicle four pillar environmental compartment (-40 ℃) |
2021 |
9 |
FAW Tropical Test Field |
|
2023 |
2.2. Preconditions
The EST scheme is based on the following prerequisites:
- The chassis dynamometer is provided by a third party and is suitable for use under environmental conditions. It also provides a cover plate for the entire base pit, and the entire chassis dynamometer will be installed in the pit.
- The speed facing fan is also supplied by the chassis dynamometer supplier.
- The peripheral devices of the environmental warehouse will be installed on the second floor equipment layer above the environmental warehouse or in the equipment room next to the environmental warehouse.
- The maximum environmental chamber heat load/cooling capacity calculated by EST is listed in the subsequent cooling capacity table.
- The foundation pit for the environmental compartment and chassis dynamometer shall be constructed by the buyer, and the seller shall provide design and drawings.
- EST provides one set of closed cooling water tower.
- The buyer will prepare appropriate ground for the cooling water tower.
- Adequate water, electricity, and gas supplies have been delivered to the designated location near the installation site.
Applicable standards:
GB 18352.6-2016 "Limits and Measurement Methods for Pollutant Emissions from Light duty Vehicles (China Phase VI)".
GB/T 19233-2020 "Test Method for Fuel Consumption of Light duty Vehicles".
GB 27999-2019 "Evaluation Methods and Indicators for Fuel Consumption of Passenger Cars"
GB/T 18386.1-2021 "Energy consumption and driving range test methods for electric vehicles - Part 1: Light vehicles"
GB/T 19753-2021 "Test Method for Energy Consumption of Light Hybrid Electric Vehicles"
GB/T 32694-2021 Technical Conditions for Plug in Hybrid Electric Passenger Cars
2.3.1 Overview of Test Cycles
Serial Number |
Regulation Number |
Regulatory name |
|
Environmental requirements |
Maximum speed (km/h) |
1 |
GB18352-2016 |
Limits and measurement methods for pollutant emissions from light-duty vehicles
|
Exhaust pollutant emission test after cold start at room temperature (Type I test)
|
Immersion temperature: 23 ℃± 3 ℃;
|
131 |
CO, THC, and NOX emissions test in exhaust after cold start at low temperatures (Type VI test)
|
Immersion temperature:- 7℃±3℃
|
78 |
2.3.2. 温度范围:-10℃ to +50℃。2.3.2. Temperature range:- 10 ℃ to+50 ℃.
2.3.3 Temperature accuracy: ± 1 ℃, no heat load, at the outlet of the speed fan.
2.3.4 Temperature accuracy: ± 1.5 ℃, steady state.
2.3.5 Temperature accuracy: ± 2.0 ℃, measured 1m on both sides at the outlet of the fan in front of the vehicle, with thermal load, steady state.
2.3.6 Cooling rate: From+50 ℃ to -10 ℃, the average rate throughout the entire process is ≥ 0.5 ℃/minute, including a load of 3 tons of vehicles.
2.3.7 Heating rate: From -10 ℃ to+50 ℃, the average rate throughout the entire process is ≥ 0.5 ℃/minute, including a load of 3 tons of vehicles.
2.3.8 Range of relative humidity
temperature |
-10℃ |
0℃ |
10℃ |
20℃ |
23℃ |
30℃ |
40℃ |
50℃ |
Relative |
-- |
-- |
100 |
100 |
100 |
95 |
63 |
38 |
Moisture |
-- |
-- |
0.0076 |
0.0147 |
0.0177 |
0.0258 |
0.03 |
0.03 |
Dew point |
-10 |
0 |
10 |
20 |
23 |
29.07 |
31.63 |
31.63 |
2.3.9 Humidity control accuracy:
No condensation, (temperature ≤ 0 ℃)
± 3%, (no empty load)
± 5%, (with vehicle empty)
2.3.3 Environmental cabin:
External dimensions: 15700x7700x5700mm (L x W x H)
Internal dimensions: 15500x7500x5500mm (L x W x H);
Insulation board thickness: 100mm hard polyurethane foam, density ≥ 40kg/M3
Outer surface: 1.0mm thickness, galvanized steel plate spray painted (milky white)
Inner surface: 1.0mm thickness, matte stainless steel plate, SUS304
Warehouse floor and pit insulation board:
The warehouse floor adopts 3/5mm patterned stainless steel SUS 304 floor Underneath the floor is a 24mm laminated board with uniform pressure. 100% hard polyurethane foam, with a galvanized spray coated steel plate containing load-bearing wooden columns at the bottom: 0.8mm. Ensure that the load-bearing capacity is: Above 1500kg/wheel.
The pit insulation board is the same as the other parts of the warehouse board:
Insulation board thickness: 100mm hard polyurethane foam, density ≥ 40kg/M3
Outer surface: 1.0mm thickness, galvanized steel plate spray painted (milky white)
Inner surface: 1.0mm thickness, stainless steel plate, SUS304
Personnel entry and exit doors and transition rooms
Large control observation window: 2000 mm x 1000 mm (W x H), Electric heating window frame anti frosting
Dynamometer cable holes: 4, Æ 100 mm
Fresh air duct hole: 1, Æ 300 mm, insulated
Exhaust pipe hole: 1, Æ 400 mm, insulated
Refrigeration pipe holes: 2, Æ 28 mm, insulated
Exhaust pipe holes: 2, Æ 54 mm, insulated
Install 2 Bitzer screw compressors with boosters.
Temperature inside the warehouse |
℃ |
-10℃ |
-7℃ |
10℃ |
15℃ |
23℃ |
50℃ |
air flow |
kg/h |
1200 |
1200 |
1200 |
2400 |
2400 |
2400 |
speed |
km/h |
120 |
120 |
140 |
160 |
130 |
130 |
Fresh Air System |
KW |
11 |
9 |
0 |
0 |
0 |
-8 |
Lighting, fans, and temperature conduction |
kW |
20 |
20 |
14 |
14 |
14 |
10 |
Automotive heat load |
kW |
72 |
72 |
101 |
139 |
217 |
217 |
Thermal load of dynamometer |
kW |
4 |
4 |
6 |
8 |
17 |
17 |
Vehicle speed fan thermal load |
kW |
36 |
36 |
57 |
86 |
86 |
86 |
Provided cooling capacity |
kW |
150 |
165 |
299 |
350 |
350 |
350 |